Modular Active Filter ADF P300

ADF P300, 100-300 A
Modular Active Filter
Overview
Overview, ADF P300 Active Filter
The ADF P300 is the ideal active filter for small and medium size commercial and industrial loads. The ADF P300 optimizes the power flow by restoring power quality. The highly valued benefits comprise lowered energy consumption, improved productivity, and reduced maintenance costs.
Active Filter with state-of-the-art performance
The state-of-the-art performance of the ADF Active Filter technology is preserved in the compact cubicle. Each ADF P300 system is delivered with 100-300 A optimization power. The modular design enables subsequent upgrades.
The ADF P300 are available in models with neutral line compensation capability designated ADF P300N.
ADF P300 family suitable where space is at a premium
ADF P300 family active filters are suitable solutions in cost-sensitive applications. With their small footprint and high power density they are optimal in applications where space is at a premium.
The ADF P300 can be configured using the built-in WUI (Web User Interface). No software needs to be installed on the laptop to perform commissioning, all that is needed is a laptop with an ethernet port and an ethernet cable.
ADF P300 delivered with functions to guarantee system safety and reliability
The ADF P300 cubicles are delivered with disconnectors, built-in automatic overload protection and software controlled monitoring functions to guarantee system safety and reliability under all operating conditions. Easy software upgrades allow the function mode to be modified without further tuning of the ADF unit.
Features
Features
Each ADF P300 active filter is customized to maximize performance in each application. The common features that all systems share include:
- Application Features
Dynamic VAR compensation
Harmonic elimination
Flicker compensation
Load balancing
Resonance elimination
Neutral compensation in 'N'-models - Control Features
Fully customizable harmonic compensation
Several ADFs can be combined for higher power
Insensitive to network conditions
Idle mode during low load
Non-overloadable
Low response time
ADF Dashboard WUI (Web User Interface) - Physical Features
Standard enclosure cabinet system, according to IP20, EN50298, EN60529, EN50102
High short circuit capacity
Simple installation
Modular and scalable design
Applications
Applications
The ADF P300 is compatible with all three phase low voltage applications. It automatically eliminates harmonics and reactive displacement in a wide range of applications. Further, the ADF P300 can be tailored to unusual applications requiring special optimizations. Some typical applications include:
- Offices and commercial buildings
- Small and medium sized manufacturing companies
- Fluorescent lamps
- Medical equipment
- Industrial loads
- UPS systems
- Fans
- Drive systems
ADF P300
Technical data - ADF P300 for industrial three phase loads
|
Model |
ADF P300-100/480 |
ADF P300-200/480 |
ADF P300-300/480 |
|---|---|---|---|
|
Rated power1 |
70 / 84 / |
139 / 167 / |
208 / 250 / |
|
Compensation current capacity at 50/60 Hz |
100 ARMS |
200 ARMS |
300 ARMS |
|
System voltage2 |
480 V (208 - 480V), 690 V (480-690V) other voltages on request |
||
|
Nominal frequency2 |
50/60 Hz ± 2% |
||
|
Number of phases |
3 |
||
|
Connection type |
3 phase without neutral (TN, TT, IT) |
||
|
Harmonic current compensated |
individual compensation up to 49th order |
||
|
Rate of harmonic |
better than 98% |
||
|
Current compensation |
up to 1.0 |
||
|
Expandability |
ADF P300 units can be used in parallel |
||
|
Response time |
< 1 ms |
||
|
Power dissipation |
< 1900 W |
< 3800 W |
< 5700 W |
|
Maximum air flow requirement |
600 m3/h |
1200 m3/h |
1800 m3/h |
|
Noise level |
< 60 dB |
||
|
Environment |
0 to 95% RH non-condensing, max altitude 1000 m |
||
|
Operating temperature |
0 to 40°C continous, <25°C recommended |
||
|
Dimensions |
800 x 2155 x 610 mm (W x H x D) |
||
|
Weight 480 V (690 V) |
324 kg (338 kg) |
450 kg (469 kg) |
576 kg (600 kg) |
|
Cabinet color |
cabinet RAL 7035 (gray), base RAL 7022 (dark gray) |
||
|
Protection class |
IP20 according to IEC 529 |
||
|
Environmental conditions |
Chemical 3C3, Mechanical 3S3 |
||
|
Electromagnetic Compatibility |
EN 61000-6-2, EN 61000-6-4 |
||
|
Certificates |
CE |
||
|
Art no 480V (690V) |
400 043 |
400 044 |
400 045 |
1 optimization capacity at 400 V nominal voltage
2 please state your system voltage and line frequency when ordering
Connection Diagram![]() |
Dimensions![]() |
ADF P300N
Technical data - ADF P300N for industrial and commercial three phase / four wire loads with neutral
|
Model |
ADF P300N-100/480 |
||
|---|---|---|---|
|
Rated power1 |
70 / 84 kVA |
||
|
Compensation current capacity at 50/60 Hz |
100 ARMS |
||
|
Compensation current capacity at 50/60 Hz, Neutral |
300 ARMS |
||
|
System voltage2 |
208 - 480 V |
||
|
System frequency2 |
50/60 Hz ± 2% |
||
|
Number of phases |
3 phases with neutral |
||
|
Connection type |
3 phase with neutral (TN, TT, IT) |
||
|
Harmonic current compensated |
individual compensation up to 49th order; 19th order in neutral |
||
|
Rate of harmonic reduction |
better than 98% |
||
|
Current compensation of cos φ |
up to 1.0 |
||
|
Expandability |
ADF P300N units can be used in parallel |
||
|
Response time |
< 1 ms |
||
|
Power dissipation |
< 3800W |
||
|
Maximum air flow requirement |
< 1200 m3/h |
||
|
Noise level |
< 60 dB |
||
|
Environment |
0 to 95% RH non-condensing, max altitude 1000 m |
||
|
Operating temperature |
0 to 40°C continous, <25°C recommended |
||
|
Dimensions |
800 x 2155 x 610 mm (W x H x D) |
||
|
Weight |
430 kg |
||
|
Cabinet color |
cabinet RAL 7035 (gray), base RAL 7022 (dark gray) |
||
|
Protection class |
IP20 according to IEC 529 |
||
|
Environmental conditions |
chemical 3C3, mechanical 3S3 |
||
|
Electromagnetic Compatibility |
EN 61000-6-2, EN 61000-6-4 |
||
|
Certificates |
CE |
||
|
Art no |
400 051 |
||
1 Compensation power at 400 V / 480 V nominal voltage
2 Please state your system voltage and line frequency when ordering
Connection Diagram![]() |
Dimensions![]() |
ADF P300W
Technical data - ADF P300W for industrial three phase loads with liquid cooling
|
Model |
ADF P300W-150/480 |
ADF P300W-300/480 |
ADF P300-450/480 |
|---|---|---|---|
|
Rated power1 |
104 / 125 / |
208 / 250 / |
312 / 375 / |
|
Compensation current capacity at 50/60 Hz |
150 ARMS |
300 ARMS |
450 ARMS |
|
System voltage2 |
480 V (208 - 480V), 690 V (480-690V) other voltages on request |
||
|
Nominal frequency2 |
50/60 Hz ± 2% |
||
|
Number of phases |
3 |
||
|
Connection type |
3 phase without neutral (TN, TT, IT) |
||
|
Harmonic current compensated |
individual compensation up to 49th order |
||
|
Rate of harmonic |
better than 98% |
||
|
Current compensation |
up to 1.0 |
||
|
Expandability |
ADF P300W units can be used in parallel |
||
|
Response time |
< 1 ms |
||
|
Power dissipation |
< 2550 W |
< 5100 W |
< 7650 W |
|
Water flow requirement |
ΔP = 66 kPa at 21 l/min | ||
|
Noise level |
< 60 dB |
||
|
Environment |
0 to 95% RH non-condensing |
||
|
Operating temperature |
0 to 50°C ambient and 38°C cooling medium temperature |
||
|
Dimensions |
800 x 2105 x 610 mm (W x H x D) |
||
|
Weight 480 V (690 V) |
367 kg (372 kg) |
500 kg (510 kg) |
633 kg (648 kg) |
|
Cabinet color |
cabinet RAL 7035 (gray), base RAL 7022 (dark gray) |
||
|
Protection class |
IP54 according to IEC 529 |
||
|
Environmental conditions |
Chemical 3C3, Mechanical 3S3 |
||
|
Electromagnetic Compatibility |
EN 61000-6-2, EN 61000-6-4 |
||
|
Certificates |
CE |
||
|
Art no 480V (690V) |
400 072 |
400 073 |
400 074 |
1 Compensation power at 400 V / 480 V / 600 V / 690 V nominal voltage
2 Please state your system voltage and line frequency when ordering
Connection Diagram![]() |